Description
Technical features
Fire detection lines:
– Maximum number of fire detectors in a line: 32
– Type of the installation: two-wire
– Maximum resistance of a line: 100 Ω
Thresholds current values:
– Fault condition: 0 – 6 mA
– Duty mode: 6 – 16 mA
– Fire condition: 16 – 80 mA
– Short circuit: > 80 mA
Monitored fire alarm lines (EN54-2, type C):
– Number: 2 pcs
– Type: potential, relay with independent control
– Electrical characteristics: (19-27.5)V DC/1A
Common fire relay outputs:
– Number: 2 pcs
– Type: potential-free,1 switching, 1 NO
– Electrical characteristics: 3А/125V AC, 3A/30V DC
Common fault warning relay outputs:
– Number: 1 pcs
– Type: potential-free, switching
– Electrical characteristics: 3А/125V AC, 3A/30V DC
Functional data:
– Identification of manual call points
– Zone dedicated label and Zone dedicated LED
indication for fire, fault, disable
– Detection for removed fire detector
– Automatic reset of the fault warning condition
– Logical “AND” scenario for fire detection lines
– EN54-2 Disabled condition and Test condition
per fire detection line and fire alarm line
– Direct mode (skip delay) function for each fire
detection line
– Test-LED functionality
– Built-in buzzer for fire and fault condition – one
tonal, continuous, can be suppressed
– Test mode for fire alarm lines
– Input for remote Reset fires operation
– 8 types optional scenarios for common fire outputs
and fire alarm outputs
– Optional delay time for fire outputs activation –
1,2,3,4,5,6 or 7 minutes
– Evacuation condition – available on access level 2
– Optional zone dedicated relay module FD4201,
each relay is common fire output corresponding
to the relevant fire detection zone