Description
Technical features
Fire detection lines (8, 16, 24 or 32):
– Maximum number of fire detectors in a line: 32
– Connecting line type: two-wire
– Maximum resistance of a line: 100 Ω
Monitored fire alarm lines (EN54-2, type C):
– Type: potential
– Electrical characteristics: (24±5)V/500 mA
Common fire relay outputs (2, 10 or 5):
– Type: potential free, switching
– Electrical characteristics: 3 A/125 V AC;
3 A/30 V DC
Common fault warning relay outputs:
– Type: potential free, switching
– Electrical characteristics: 3 A/125 V AC;
3 A/30 V DC
Indications of registered events:
– Light indication: LEDs
– Text messages: LCD display – 4 lines,
20 symbols
– Sound: Built-in buzzer
Access levels to control functions:
– 4 (in compliance with EN 54/2)
Power supply:
– Mains: 220/230 V
– Frequency: 50 Hz
Backup batteries:
– 2 x 12 V / 12 Ah
Operation in duty mode upon interrupted mains
supply:
– Minimum configuration: 80 h
– Maximum configuration 30 h
Consumption on backup batteries supply in
duty mode at 24 V:
– Minimum configuration: <155 mA
– Maximum configuration: <400 mA
Power supply to external devices:
– Voltage: (24±5)V
– Maximum output current (current of controllable
outputs included): 1,5 A
Weight (backup batteries not included): 6,6 kg
Dimensions: 450 x 355 x 115 mm
Operating temperature: -5 °C to +40 °C
Relative humidity: to 93%
Degree of protection: IP 40
Functional data:
– Automatic reset of the fault warning condition
– Logical “AND” scenario for fire detection lines
– Fully programmable from the display user-friendly
menu structure
– Modular fire alarm panel with optional modules for fire
detection lines and fire alarm lines
– Optional scenarios for common fire outputs and fire
alarm outputs
– Compatible with third party fire detectors with the
zone-individual programmable threshold current values
– Real time clock and Event log of 2500 events
Reviews